The DPI includes the following field selectable features:
• Configurable switching point: Open on rise or fall in pressure
• Hysteresis of setpoint
• Measurement units (Pa, kPa, mmWC, inWC, mbar)
• Measurement range (4 ranges per model)
• Output signal (0−10 V, NO/NC)
• Span and zero point calibration
There are no reviews yet.
Questions and answers of the customers
There are no questions yet, be the first to ask something for this product.
Technical specifications
Measurement ranges: 100 / 250 / 1000 / 2500 Pa (field selectable via menu)
Accuracy: ±1.5 % (±0.7 %*)
Long term stability: Typical 1 year With autozero: ±1 Pa Without autozero: ±8 Pa
Electrical connections:
in/out:
Terminal block (24 V, GND, 0–10 V)
Wire: 0.2–1.5 mm2 (12–24 AWG)
Relay 1:
Terminal block (NC, COM, NO)
Wire: 0.2–1.5 mm2 (12–24 AWG)
Relay 2:
Terminal block (NC, COM, NO)
Wire: 0.2–1.5 mm2 (12–24 AWG)
Electrical
Circuit: 3-wire (24 V, GND, 0–10 V)
Input:
Without autozero: 21–35 VDC/ 24 VAC, ±10 %
With autozero: 24 VAC or VDC, ±10 %
Output:
Analog: 0–10 V
Relay 1: 250 VAC / 30 VDC / 6 A
Relay 2: 250 VAC / 30 VDC / 6 A
Adjustable switching point and hysteresis
Zero/Span output calibrated within ±0.025 V
Resistance minimum: 1 kΩ
Current consumption: 35 mA + relays (7 mA each) + AZ circuit (20 mA)
+ 0–10 V output (10 mA)
Be the first to review “HK Instruments : DPI2500-2R-AZ-D Electronic differential pressure transmitter 2500Pa with 2Relays”
You must be logged in to post a review.